Measuring Transducers
Current Inputs
Value Setting Range
Rated current measuring range ± 20 mA
Maximum current measuring range ± 24 mA
Tolerances
•
without trimming
•
with offset trimming
•
with full trimming
± 124 μA (0.62 % at 20 mA)
± 60 μA (0.3 % at 20 mA)
± 20 μA (0.1% at 20 mA)
Sampling rate ≥ 3 Hz
Number of channels per measuring transducer
module
2 or 4
Analog-digital converter 16 Bit Sigma/Delta
12.33
Technical Data
12.33 Measuring Transducers 