Siemens SIPROTEC 5 6MU85 - 12.10.9 Overvoltage Protection with Negative-Sequence Voltage;Positive-Sequence Voltage

Siemens SIPROTEC 5 6MU85
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dropout time, typical Approx. 25 ms + OOT
Dropout time, maximum Approx. 30 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 90 Hz
Slightly expanded tolerances
f < 10 Hz
f > 90 Hz
Inactive, maintained;
Dropout of the pickup induced by blocking or by increasing the
measurand beyond the dropout threshold
Tolerances
Voltages 0.5 % of the setting value or 0.05 V
Time delays 1 % of the setting value or 10 ms
Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence
Voltage
Setting Values for the Function
Measuring window
1 cycle to 10 cycles Increments of 1 cycle
Minimum voltage V1 0.300 V to 60.000 V Increments of 0.001 V
Setting Values for Stage Types
Pickup value of V2/V1
0.50 % to 100.00 % Increments of 0.01 %
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Pickup times
55 ms to 210 ms + OOT
69
(depends on the measuring-window length) at 50 Hz
48 ms to 190 ms + OOT
(depends on the measuring-window length) at 60 Hz
Dropout times 22 ms to 55 ms + OOT
(depends on the measuring-window length) at 50 Hz
18 ms to 45 ms + OOT
(depends on the measuring-window length) at 60 Hz
12.10.9
69
OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Technical Data
12.10 Voltage Protection
SIPROTEC 5, Merging Unit 6MU85, Manual 843
C53000-G5040-C074-1, Edition 01.2020