Trip-Circuit Supervision
Setting Values
Number of monitored circuits per circuit-breaker function group 1 to 3
Operating mode per circuit With 1 binary input
With 2 binary inputs
Pickup and dropout time Approx. 1 s to 2 s
Adjustable indication delay with 1 binary input 1.00 s to 600.00 s Increments of 0.01 s
Adjustable indication delay with 2 binary inputs 1.00 s to 30.00 s Increments of 0.01 s
12.28
Technical Data
12.28 Trip-Circuit Supervision
864 SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020