EasyManua.ls Logo

Siemens SIPROTEC 5 6MU85 - Page 38

Siemens SIPROTEC 5 6MU85
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Up to 50th harmonic, f
rated
= 50 Hz 2 % of the setting value or 10 mA (I
rated
= 1 A)
or 50 mA (I
rated
= 5 A), (f
rated
± 10 %)
Up to 50th harmonic, f
rated
= 60 Hz 3 % of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation
40
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic 1.5 % of the setting value or 10 mA (I
rated
= 1 A)
or 50 mA (I
rated
= 5 A), (f
rated
± 10 %)
41
Up to 50th harmonic, f
rated
= 50 Hz 3% of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
42
Up to 50th harmonic, f
rated
= 60 Hz 4 % of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
43
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Time delays 1 % of the setting value or 10 ms
Influencing Variables for Thresholds
Transient excess pickup in method of measurement =
fundamental component, for τ > 100 ms (with
complete unbalance)
< 5 %
40
In case that the filter response exactly matches the user-defined gain factors
41
In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
42
In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
43
In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
Technical Data
12.6 Overcurrent Protection, Phases
SIPROTEC 5, Merging Unit 6MU85, Manual 815
C53000-G5040-C074-1, Edition 01.2020