Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for 2 ≤ I/threshold value I ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Influencing Variables for Thresholds
Transient excess pickup in method of measurement =
fundamental component, for τ > 100 ms (with
complete unbalance)
< 5 %
Technical Data
12.7 Overcurrent Protection, Ground
824 SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020