EasyManuals Logo

Siemens SIPROTEC 5 7VE85 User Manual

Siemens SIPROTEC 5 7VE85
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
Date and Time Synchronization
Date format DD.MM.YYYY (Europe)
MM/DD/YYYY (USA)
YYYY-MM-DD (China)
Time source 1, time source 2 None
IRIG-B 002(003)
IRIG-B 006(007)
IRIG-B 005(004) with extension according to
IEEE C37.118-2005
DCF77
PI (protection interface)
27
SNTP
IEC 60870-5-103
DNP3
IEEE 1588
T104
Time zone 1, time zone 2 Local
UTC
Failure indication after 0 s to 3600 s
Time zone and daylight saving time Manually setting the time zones
Time zone offset with respect to GMT -720 min to 840 min
Switching over to daylight saving time Active
Inactive
Beginning of daylight saving time Input: day and time
End of daylight saving time Input: day and time
Offset daylight saving time 0 min to 120 min [steps of 15]
12.2
27
If provided
Technical Data
12.2 Date and Time Synchronization
SIPROTEC 5, Paralleling Device, Manual 717
C53000-H5040-C071-1, Edition 05.2018

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 7VE85 and is the answer not in the manual?

Siemens SIPROTEC 5 7VE85 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 5 7VE85
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals