EasyManua.ls Logo

Siemens SIPROTEC 5 7VE85 - Page 63

Siemens SIPROTEC 5 7VE85
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Active
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the setting value or 10 ms
Technical Data
12.18 Circuit-Breaker Failure Protection
SIPROTEC 5, Paralleling Device, Manual 763
C53000-H5040-C071-1, Edition 05.2018