A.9 Information List
599
7UT613/63x Manual
C53000-G1176-C160-2
325.2503 >BLOCK IE> time overcurrent 2
(>BLOCK IE-2>)
Earth O/C 2 SP * * * LED BI BO
325.2504 >BLOCK IEp time overcurrent 2
(>BLOCK IE-2p)
Earth O/C 2 SP * * * LED BI BO
325.2514 Time Overcurrent Earth 2 IE>>
BLOCKED (IE-2>> BLOCKED)
Earth O/C 2 OUT ON
OFF
ON
OFF
* LED BO
325.2515 Time Overcurrent Earth 2 IE>
BLOCKED (IE-2> BLOCKED)
Earth O/C 2 OUT ON
OFF
ON
OFF
* LED BO
325.2516 Time Overcurrent Earth 2 IEp
BLOCKED (IE-2p BLOCKED)
Earth O/C 2 OUT ON
OFF
ON
OFF
* LED BO
325.2521 Time Overcurrent Earth 2 IE>>
picked up (O/C E2 IE>> PU)
Earth O/C 2 OUT * ON
OFF
* LED BO
325.2522 Time Overcurrent Earth 2 IE>
picked up (O/C E2 IE> PU)
Earth O/C 2 OUT * ON
OFF
* LED BO
325.2523 Time Overcurrent Earth 2 IEp
picked up (O/C E2 IEp PU)
Earth O/C 2 OUT * ON
OFF
* LED BO
325.2524 Time O/C Earth 2 IE> InRush
picked up (IE-2> InRushPU)
Earth O/C 2 OUT * ON
OFF
* LED BO
325.2525 Time O/C Earth 2 IEp InRush
picked up (IE-2p InRushPU)
Earth O/C 2 OUT * ON
OFF
* LED BO
325.2529 Earth 2 InRush picked up (Earth2
InRushPU)
Earth O/C 2 OUT * ON
OFF
* LED BO
325.2541 Time Overcurrent Earth 2 IE>>
Time Out (IE-2>> Time Out)
Earth O/C 2 OUT * * * LED BO
325.2542 Time Overcurrent Earth 2 IE>
Time Out (IE-2> Time Out)
Earth O/C 2 OUT * * * LED BO
325.2543 Time Overcurrent Earth 2 IEp
Time Out (IE-2p Time Out)
Earth O/C 2 OUT * * * LED BO
325.2551 Time Overcurrent Earth 2 IE>>
TRIP (O/C E2 IE>>TRIP)
Earth O/C 2 OUT * ON * LED BO
325.2552 Time Overcurrent Earth 2 IE>
TRIP (O/C E2 IE> TRIP)
Earth O/C 2 OUT * ON * LED BO
325.2553 Time Overcurrent Earth 2 IEp
TRIP (O/C E2 IEp TRIP)
Earth O/C 2 OUT * ON * LED BO
326.2413 Dynamic settings O/C Earth-2 are
ACTIVE (IE-2 Dyn.s. ACT)
ColdLoadPickup OUT ON
OFF
ON
OFF
* LED BO
361 >Failure: Feeder VT (MCB
tripped) (>FAIL:Feeder VT)
Supervision SP ON
OFF
ON
OFF
* LED BI BO 150 38 1 Yes
390 >Warning stage from gas in oil
detector (>Gas in oil)
Ext. Tansf.Ann. SP ON
OFF
**LEDBIBO
391 >Warning stage from Buchholz
protection (>Buchh. Warn)
Ext. Tansf.Ann. SP ON
OFF
* * LED BI BO 150 41 1 Yes
392 >Tripp. stage from Buchholz pro-
tection (>Buchh. Trip)
Ext. Tansf.Ann. SP ON
OFF
* * LED BI BO 150 42 1 Yes
393 >Tank supervision from Buchh.
protect. (>Buchh. Tank)
Ext. Tansf.Ann. SP ON
OFF
* * LED BI BO 150 43 1 Yes
409 >BLOCK Op Counter (>BLOCK
Op Count)
Statistics SP ON
OFF
**LEDBIBO
501 Relay PICKUP (Relay PICKUP) P.System Data 2 OUT * ON M LED BO 150 151 2 Yes
511 Relay GENERAL TRIP command
(Relay TRIP)
P.System Data 2 OUT * ON M LED BO 150 161 2 Yes
545 Time from Pickup to drop out (PU
Time)
P.System Data 2 VI
546 Time from Pickup to TRIP (TRIP
Time)
P.System Data 2 VI
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation