Messages and diagnostics
7.2 Function Codes
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
109
Example
Setting the rated operational current Ie to 100 A:
Address Field or slave address: The address of the 3RW5 soft starter is not entered in
the example (-).
The CRC CHECK is not entered in the example (-).
The register address of the rated operational current Ie is 0x9403.
The rated operational current Ie occupies 2 registers.
The value 100 A is transmitted to the 3RW5 soft starter (0x0000 0x2710).
You can find the data table for the parameters in Parameters (Page 164).