Configuring
6.3 Configuring the 3RW5 Soft Starter
SIRIUS 3RW5 Modbus communication module
84 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
6.3.2.5 Port configuration and baud rate
Setting options
SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created
Soft Starter > "Parameters" > Window "Work area" > "Communication module >
Interface"
Further information on the operation of SIRIUS Soft Starter ES (TIA Portal) can be found
in the online help of SIRIUS Soft Starter ES (TIA Portal).
3RW5 HMI High Feature
Menu: "Parameter > Communication module > Modbus RTU > Port configuration"
Menu: "Parameter > Communication module > Modbus RTU > Baud rate"
You will find more information on operating the 3RW5 HMI High Feature in the
Equipment Manual of the 3RW5 soft starter.
User program via the "Modbus RTU communication parameters" data table (Page 177)
Parameters
Parameter
Description
Port configuration
Automatic
1 start, 8 data, 1 stop bit, even parity (factory setting)
1 start, 8 data, 1 stop bit, odd parity
1 start, 8 data, 2 stop bit, no parity
1 start, 8 data, 1 stop bit, no parity
Baud rate
Automatic
115.2 kbit/s
76.8 kbit/s
57.6 kbit/s
38.4 kbit/s
19.2 kbit/s (factory setting)
9.6 kbit/s
4.8 kbit/s
2.4 kbit/s
1.2 kbit/s