A.2.20 Modbus RTU communication parameters
Read access (r) to the communication parameters is possible via Function Codes 03 and 04.
Write access (w) is possible for individual communication parameters via Function Codes 06
and 16.
Range of values
[encoding]
0xA202
[41474]
high Unsigned32 Access monitoring
time
[5 000 ... 10 000] 5 000 r/w
[5 000] 5 s
0xA204
[41476]
high Unsigned16 Silent interval time Increment: 0.1 ms 0
1)
r/w
Baud rate: 1.2 kbit/s 32 ... 6 553.5 ms
Baud rate: 2.4 kbit/s 16 ... 6 553.5 ms
Baud rate: 4.8 kbit/s 8 ... 6 553.5 ms
Baud rate: 9.6 kbit/s 4 ... 6 553.5 ms
Baud rate: 19.2 kbit/s 2 ... 6 553.5 ms
Baud rate: 38.4 kbit/s 1 ... 6 553.5 ms
Baud rate: 57.6 kbit/s 0.7 ... 6 553.5 ms
Baud rate: 76.8 kbit/s 0.5 ... 6 553.5 ms
Baud rate: 115.2 kbit/s 0.3 ... 6 553.5 ms
1)
0xA206
[41478]
high Unsigned8 Baud rate [0 ... 12] 8 r/w
[0] Automatic
[1] 115.2 kbit/s
[4] 76.8 kbit/s
[6] 57.6 kbit/s
[7] 38.4 kbit/s
[8] 19.2 kbit/s
[9] 9.6 kbit/s
[10] 4.8 kbit/s
[11] 2.4 kbit/s
low Unsigned8 Port configuration
1 r/w
[0] Automatic
[1] 1 start, 8 data, 1 stop bit, even parity
[2] 1 start, 8 data, 1 stop bit, odd parity
[3] 1 start, 8 data, 2 stop bit, no parity
[4] 1 start, 8 data, 1 stop bit, no parity