Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
178 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Register
Byte
Data format
Parameter
Range of values
[encoding]
Default
Access
Address
high /
low
0xA207
[41479]
high Unsigned8 Station address 1 ... 247
[1 ... 247]
126 r/w
0xA208
[41480]
high Unsigned8 Detected baud rate
[0 ... 12]
- r
[0] Automatic
[1] 115.2 kbit/s
[4] 76.8 kbit/s
[6] 57.6 kbit/s
[7] 38.4 kbit/s
[8] 19.2 kbit/s
[9] 9.6 kbit/s
[10] 4.8 kbit/s
[11] 2.4 kbit/s
[12] 1.2 kbit/s
low Unsigned8 Detected port
configuration
[0 ... 4]
- r
[0] Automatic
[1] 1 start, 8 data, 1 stop bit, even parity
[2] 1 start, 8 data, 1 stop bit, odd parity
[3] 1 start, 8 data, 2 stop bit, no parity
[4] 1 start, 8 data, 1 stop bit, no parity
1)
For the value "0" ("Automatic"), the minimum silent interval time of the baud rate used is automatically set.