Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
138 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
A.2.3 Memory image
ddress range Chapter Length 3RW
hex dec 50 /
52
1)
55 /
55-F
2)
Commands
0x0000 0 Node flash test (Page 140) 1 register x x
Identification data
0x00C1 - 0x00E0 193 - 224 I&M0 - device identification
(3RW5 communication module) (Page 141)
32 registers x
3),
4)
x
3), 4)
0x0181 - 0x01A0 385 - 416 I&M0 - device identification (3RW5 soft starter)
(Page 142)
32 registers x x
0x01A1 - 0x1C0 417 - 448 I&M1 - equipment identifier (3RW5 soft Starter)
(Page 143)
32 registers x x
0x01C1 - 0x01E0 449 - 480 I&M2 - installation (3RW5 soft starter) (Page 144) 32 registers x x
0x01E1 - 0x0200 481 - 512 I&M3 - description (3RW5 soft starter) (Page 145) 32 registers x x
0x0241 - 0x0260 577 - 608 I&M0 - device identification (3RW5 HMI High Feature)
(Page 146)
32 registers x
5)
x
5)
Energy management (Page 147)
0x09C1 - 0x09C2 2497 - 2498 Phase current I L1 (rms) 2 registers x x
0x09C3 - 0x09C4 2499 - 2500 Phase current I L2 (rms) 2 registers x x
0x09C5 - 0x09C6 2501 - 2502 Phase current I L3 (rms) 2 registers x x
0x09C7 - 0x09C8 2503 - 2504 Phase current average (rms) 2 registers x x
0x0A47 - 0x0A48 2631 - 2632 Active power 2 registers - x
0x0A61 - 0x0A62 2657 - 2658 Active energy import (total) 2 registers - x
3RW5 soft starter
0x8000 - 0x8007 32768 - 32775 Process image input (PII) (Page 148) 8 registers x x
0x8200 - 0x8201 33280 - 33281 Process image output (PIQ) (Page 150) 2 registers x x
0x8400 - 0x8429 33792 - 33833 Soft starter diagnostics (Page 152) 42 registers x x
0x8800 - 0x882C 34816 - 34860 Measured values (Page 158) 45 registers x x
0x8C00 - 0x8C5E 35840 - 35934 Statistic data (Page 160) 95 registers x
6)
x
0x9000 - 0x9039 36864 - 36921 Maximum pointer (Page 162) 58 registers x
6)
x
0x9400 - 0x945E 37888 - 37982 Parameters (Page 164) 95 registers - x
Communication (for 3RW5 Modbus TCP communication module only)
0xA100 - 0xA116 41216 - 41238 Communication parameters Modbus TCP (Page 176) 23 registers x
3)
x
3)
Communication (for 3RW5 Modbus RTU communication module only)
0xA200 - 0xA209 41472 - 41481 Modbus RTU communication parameters (Page 177) 10 registers x
4)
x
4)