Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
148 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
A.2.12 Process image input (PII)
For access to the process image input (PII) only read access (r) is possible via Function
Codes 01, 02, 03, 04 and 23.
Register Byte Bit address Data
format
Process image 3RW
Address high / low hex dec 50 /
52
1)
55 /
55-F
2)
0x8000
[32768]
high 0x8000 32768 Bool Ready (automatic) r r
0x8001 32769 Bool Motor On r r
0x8002 32770 Bool Group error r r
0x8003 32771 Bool Group warning r r
0x8004 32772 Bool Input 1 r r
0x8005 32773 Bool Input 2 - r
0x8006 32774 Bool Input 3 - r
0x8007 32775 Bool Input 4 - r
low 0x8008 32776 Bool Motor current Iact-bit0 r r
0x8009 32777 Bool Motor current Iact-bit1 r r
0x800A 32778 Bool Motor current Iact-bit2 r r
0x800B 32779 Bool Motor current Iact-bit3 r r
0x800C 32780 Bool Motor current Iact-bit4 r r
0x800D 32781 Bool Motor current Iact-bit5 r r
0x800E 32782 Bool Operating mode manual - local r r
0x800F 32783 Bool Ramp operation r r
0x8001
[32769]
high 0x8010 32784 Bool Motor CW r r
0x8011 32785 Bool Motor CCW - r
0x8014 32788 Bool Starting mode active r r
0x8015 32789 Bool Operation / bypass active r r
0x8016 32790 Bool Stopping mode active r r
0x8017 32791 Bool Test mode active r
3)
r
low 0x8018 32792 Bool Thermal motor model overload r r
0x8019 32793 Bool Temperature sensor overload r r
0x801A 32794 Bool Switching element overload r r
0x801B 32795 Bool Cooling time active r r
0x801C 32796 Bool Device error r r
0x801D 32797 Bool Automatic parameterization active - r
0x801E 32798 Bool New EX parameter values detected - r
4)