A.2 Data tables
SIRIUS 3RW5 Modbus communication module
154 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Register Byte Bit address Data format Soft starter diagnostics 3RW Type
5)
A
ddress high / low hex dec 50
1)
52
2)
55
3)
55-F
4)
0x8406
[33798]
high 0x8463 33891 Bool Preset unequal actual
configuration
r r r r ER
0x8465 33893 Bool Temperature sensor overload - - r r MT
0x8466 33894 Bool Temperature sensor wire break - - r r MT
0x8467 33895 Bool Temperature sensor short-circuit - - r r MT
low 0x8468 33896 Bool Parameter set 1 active - - r r -
0x8469 33897 Bool Parameter set 2 active - - r r -
0x846A 33898 Bool Parameter set 3 active - - r r -
0x846C 33900 Bool Parameter set change not
possible
- - r r -
0x846E 33902 Bool Preset unequal actual
configuration
- - r r MT
0x846F 33903 Bool Motor connection wrong - - r r ER
0x8407
[33799]
high 0x8472 33906 Bool Motor heating active - - r - -
0x8473 33907 Bool DC braking active - - r - -
0x8474 33908 Bool Dynamic DC braking active - - r - -
0x8475 33909 Bool Type of motor connection
standard
r r r r -
0x8476 33910 Bool Type of motor connection inside
delta
- r r r -
0x8477 33911 Bool Type of motor connection
unknown
r r r r -
low 0x8478 33912 Bool Missing load r r r r ER
0x847A 33914 Bool Loss of phase L1 r r r r ER
0x847B 33915 Bool Loss of phase L2 r r r r ER
0x847C 33916 Bool Loss of phase L3 r r r r ER
0x847D 33917 Bool Main power rotation right r r r r -
0x847E 33918 Bool Main power rotation left r r r r -
0x8408
[33800]
low 0x8488 33928 Bool Output 1 active r r r r -
0x8489 33929 Bool Output 2 active r r r r -
0x848A 33930 Bool Output 3 active r r r r -
0x848B 33931 Bool Output 4 active - - r r -
0x848C 33932 Bool Output 1 - Time active - - r r -
0x848D 33933 Bool Output 2 - Time active - - r r -
0x848F 33935 Bool Output 4 - Time active - - r - -
0x8409
[33801]
low 0x8499 33945 Bool Ready to start for motor ON r r r r -
0x849B 33947 Bool Bypass defective r r r r ER
0x849C 33948 Bool Bypass protective shutoff r r r r ER
0x849D 33949 Bool Switching element L1 failed r r r r ER
0x849E 33950 Bool Switching element L2 failed - r r r ER
0x849F 33951 Bool Switching element L3 failed r r r r ER