Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
156 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Register Byte Bit address Data format Soft starter diagnostics 3RW Type
5)
ddress high / low hex dec 50
1)
52
2)
55
3)
55-F
4)
0x841A
[33818]
high 0x85A2 34210 Bool Remaining time for tripping
warning limit undershot
- - r r MT
0x85A3 34211 Bool Motor heating warning limit
exceeded
r r r r MT
0x85A4 34212 Bool Current limit - maintenance
demanded exceeded
- - r r MT
0x85A5 34213 Bool Current limit - maintenance
demanded undershot
- - r r MT
0x85A6 34214 Bool Asymmetry limit warning
exceeded
- - r r MT
0x85A7 34215 Bool Ground fault limit warning
exceeded
- - r r MT
0x841B
[33819]
low 0x85B8 34232 Bool Pump cleaning active - - r r -
0x841C
[33820]
high 0x85C5 34245 Bool Analog output underflow - - r r -
low 0x85CD 34253 Bool Analog output overflow - - r r -
0x841E
[33822]
high 0x85E0 34272 Bool Missing initialization after
maintenance
r r r r -
low 0x85E8 34280 Bool Switching frequency time
running
- - r r -
0x85E9 34281 Bool Switching frequency time not
kept
- - r r ER
0x85EB 34283 Bool Switching frequency time not
kept
- - r r MT
0x85EF 34287 Bool Switching frequency lock active - - r r -
0x841F
[33823]
high 0x85F2 34290 Bool Emergency start enabled - - r r -
0x85F4 34292 Bool Emergency run enabled - - r
9)
- -
0x85F5 34293 Bool Emergency run active - - r
9)
- -
low 0x85F8 34296 Bool 2-phase control with defective
thyristor active
- - r
9)
- MT
0x85F9 34297 Bool Alternative stopping mode active - - r r -
0x8420
[33824]
high 0x8600 34304 Bool Reversing DC braking active - - r
8)
- -
low 0x8608 34312 Bool Main power rotation faulty - - r r ER
0x860B 34315 Bool Main power rotation faulty - - r r MT
0x8421
[33825]
low 0x861D 34333 Bool Check fan r r r r MT