Technical data
6.2 Output
SITOP SEL1200-1400
Manual, 06.2019, A5E46496083-1-76
39
The following applies for the SEL1400: In the range > 150 % of the selected current
response threshold, the current is limited to 150 %, typically after 10 ms to 100 ms, the
output is electronically shut down (LED of the output is lit red).
● An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
● In the range 100 - 150 % of the selected current response threshold, an overload current
is permissible for 5 seconds (LED of the output flashes green), then the output is
electronically shut down (LED of the output is lit red).