Technical data
6.2 Output
SITOP SEL1200-1400
Manual, 06.2019, A5E46496083-1-76
39
The following applies for the SEL1400: In the range > 150 % of the selected current
response threshold, the current is limited to 150 %, typically after 10 ms to 100 ms, the
output is electronically shut down (LED of the output is lit red).
An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
In the range 100 - 150 % of the selected current response threshold, an overload current
is permissible for 5 seconds (LED of the output flashes green), then the output is
electronically shut down (LED of the output is lit red).