EasyManua.ls Logo

Siemens SITOP SEL1200 - Output Data

Siemens SITOP SEL1200
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
6.2 Output
SITOP SEL1200-1400
38 Manual, 06.2019, A5E46496083-1-76
6.2 Output
6EP4438-7FB00-3DX0
6EP4438-7EB00-3DX0
Output
Regulated DC voltage
Output voltage
U
out
= U
in
- approx. 0.5 V
Total tolerance
Corresponding to the supplying input voltage
Number of outputs
8
Output current up to 60 °C for each output (rated value)
Remark
10 A (in total, not more than 60 A)
60 ... 70 °C derating: 2 % I
out
/K
Adjustable response threshold
2 - 10 A
Connecting outputs in parallel
Yes, max. 4 × 2 outputs each that must lie next to one another.
Switching on outputs All outputs are switched-on after the supply voltage ramps up
> 20 V, delay time of 25 ms, 200 ms, 500 ms – or "load opti-
mized", selectable using DIP switch.
Shutdown characteristics:
Figure 6-1 Shutdown characteristic
The following applies for the SEL1200: In the range > 150 %, a higher current is briefly
permitted; afterwards it is shut down corresponding to the "Shutdown characteristic"
diagram.

Related product manuals