Parameterizing the SITOP UPS1600
6.2 Switching off the UPS by a user program when the power fails
SITOP UPS1600 under STEP 7 V5
40 Getting Started,
Procedure
1. In the program folder of your project, open the symbol table "Symbols_UPS1600".
2. Match the addresses of the following symbols with the selected I/O address areas of the
corresponding UPS1600 parameters:
UPS_Battery_charge_level
UPS_Buffer_mode
UPS_New_alarms_pending
UPS_Ready_for_buffering
3. Save the project and load the parameters into the S7 IO controller.
When the power fails, the user program now switches off the UPS.