Parameterizing the SITOP UPS1600
6.2 Switching off the UPS by a user program when the power fails
SITOP UPS1600 under STEP 7 V5
Getting Started,
39
Adapting the symbol table/address area
When function block FB160 is executed, the cyclic data of address area of UPS1600 is
accessed. In this particular case, the required address areas are transferred to the function
block via four variables. You must adapt the addresses of these variables corresponding to
your selected address area in the symbol table of the code block package.
The following table shows the I/O address area of the UPS1600, which is used within the
function block.
Note
You can find the setting of the I/O address area for the UPS1600 in the HW Config of
the
Simatic station that you created.
Variable in the symbol table
UPS1600 parameters
Information
Address area in the
following example
UPS_battery_charge_level battery_charge level Charging state of
the battery
PEB 262
UPS_Buffer_mode buffer mode Buffer mode/
normal mode
PEB 257
UPS_New_alarms_pending New alarms pending New / no pending
alarms
PEB 261
UPS_Ready_for_buffering ready for buffering Ready for
buffering / not
ready
PEB 258
Note
You can find additional information on the I/O address
area of the UPS1600 in the UPS1600
Manual.