SITRANS FC410 flowmeter
A5E33120231-001, 12/2013 5
Install two supports or hangers symmetrically and stress-free on the pipeline in close proximity to the process
connections.
Note
Handling
Never lift the flowmeter using the housing, that is always lift the sensor body.
Avoid vibrations
Make sure that any valves or pumps upstream of the sensor do not cavitate and do not send vibrations into the sensor.
Decouple vibrating pipeline from the flow sensor using flexible tube or couplings.
Figure 3-7 Non-flexible pipes not recommended in vibrating environment
Figure 3-8 Flexible pipes recommended in vibrating environment
Avoid cross talk
If operating more than one flowmeter in one or multiple interconnected pipelines there is a risk of cross talk.
Prevent cross talk in one of the following ways:
Mount sensors on separate frames
Decouple the pipeline using flexible tube or couplings
Figure 3-9 High risk of cross talk when using non-flexible pipes
Figure 3-10 Low risk of cross talk when using flexible pipes and separate frames