SITRANS P DS III (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434626-03, 06/2013
21
4.2
Connecting the device
Opening the device
1. Unscrew the cover of the electrical cable compartment. An identification text "FIELD TERMINAL" is provided at the side
of the housing.
Connecting the device
1. Lead the connecting cable through the cable gland .
2. Connect the device to the plant with the protective conductor connection .
3. Connect the wires to the connecting terminals
"+" and "-".
Ensure the correct polarity! If necessary, ground the device using the "-" connection by connecting the "-" connection to
the ground terminal .
4. If necessary, connect the shield to the screw of the ground terminal
. This is electrically connected with the external
protective conductor connection.
HART
PROFIBUS PA / Foundation™ Fieldbus FF
Feed separator with integrated load
Safety catch
Auxiliary power
Protective conductor connection/
equipotential bonding terminal
Cable entry for auxiliary power/analog output
Process connection
Connecting terminals
Ground terminal
Test connector for direct current measuring device or
connection for external display
PROFIBUS PA / Foundation™ Fieldbus FF