SITRANS P DS III (7MF4.33.. 7MF4.34.. 7MF4.35..)
30 A5E03434626-03, 06/2013
5.4.4
Commissioning with vapor
Pressure transmitter
Drain valves
Stabilizing valve
Condensate pots
,
Differential pressure valves
Differential pressure transducer/Orifice plate
Differential pressure lines
Insulation
Shut-off valves
Figure 5-2 Measuring steam
Condition
All valves are closed.
Procedure
WARNING
Hot vapor
Danger of injury or damage to device.
If the shut-off valves
and the differential pressure valve are both open and the stabilizing valve is then opened,
the transmitter
can be damaged by the flow of vapor.
Follow the specified procedure for commissioning.
WARNING
Hot vapor
Danger of injury.
You can briefly open the drain valves
to clean the line. Hot vapor can escape in the process.
Only open the drain valves briefly, and close them again before vapor escapes.
To commission the transmitter for vapor, proceed as follows:
1. Open both the shut-off valves
at the pressure tapping point.
2. Open the stabilizing valve
.
3. Wait until the steam in the differential pressure lines
and in the equalizing vessels has condensed.