SITRANS P DS III (7MF4.33.. 7MF4.34.. 7MF4.35..)
30 A5E03434626-03, 06/2013
Differential pressure valves
Differential pressure transducer/Orifice plate
Differential pressure lines
Figure 5-2 Measuring steam
All valves are closed.
Danger of injury or damage to device.
If the shut-off valves
⑥ and the differential pressure valve ③ are both open and the stabilizing valve ② is then opened,
the transmitter
① can be damaged by the flow of vapor.
Follow the specified procedure for commissioning.
Danger of injury.
You can briefly open the drain valves
⑦ to clean the line. Hot vapor can escape in the process.
Only open the drain valves ⑦ briefly, and close them again before vapor escapes.
To commission the transmitter for vapor, proceed as follows:
1. Open both the shut-off valves
⑥ at the pressure tapping point.
2. Open the stabilizing valve
②.
3. Wait until the steam in the differential pressure lines
⑤ and in the equalizing vessels ⑧ has condensed.