SITRANS P DS III (7MF4.33.. 7MF4.34.. 7MF4.35..)
40 A5E03434626-03, 06/2013
Conditions of use for gauge pressure and absolute pressure with flush-mounted diaphragm
Process medium conditions
Process temperature
1)
Measuring cell with silicone oil
filling
-40 … +150°C (-40 … +302 °F)
-40 … +200°C (-40 … +392 °F) with cooling extension
Measuring cell with inert liquid
-20 … +100 °C (-4 … +212 °F)
-20 … +200°C (-4 … +392 °F) with cooling extension
Measuring cell with Neobee
(FDA-compliant)
-10 … +150°C (14 … 302 °F)
-10 … +200°C (14 … 392 °F) with cooling extension
Measuring cell with high-
temperature oil filling
-10 ... +250 °C (14 ... 482 °F) with cooling extension
1)
Observe the temperature limits in the process connection standards (e.g. DIN 32676 and DIN 11851) for the maximum
process temperature for flush-mounted process connections.
Rated conditions DS III with PMC connection
Installation conditions
Ambient temperature
Note
Observe the temperature class in hazardous areas.
Measuring cell with silicone oil
filling
-40 … +85 °C (-40 … +185 °F)
Display
-30 … +85 °C (-22 … +185 °F)
Storage temperature
-50 … +85 °C (-58 … +185 °F)
Climate class
Condensation
Permitted
Degree of protection in
accordance with EN 60529
IP65, IP68
Degree of protection in
accordance with NEMA 250
NEMA 4X
Electromagnetic compatibility
Interference emission and
interference immunity
In accordance with EN 61326 and NAMUR NE 21
Process medium conditions
Process temperature
-40 … +100 °C (-40 … +212 °F)
Rated conditions for absolute pressure (from the differential pressure series), differential pressure and flow rate
Installation conditions
Installation instruction
any
Ambient conditions
Ambient temperature
Note Observe the temperature class in hazardous areas.
Measuring cell with silicone oil
filling
-40 … +85 °C (-40 … +185 °F)
Measuring cell
30 bar (435 psi)
-20 … +85 °C (-4 … +185 °F)
With flow: -20 … +85 °C (-4 … +185 °F)
Measuring cell with inert liquid
-20 … +85 °C (-4 … +185 °F)
Display
-30 … +85 °C (-22 … +185 °F)
Storage temperature
-50 … +85 °C (-58 … +185 °F)
Climate class
Condensation
Permitted