3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
Upper fault current parameter
Adjusts the magnitude of the upper fault current .
Setting range: Between upper saturation limit und 22.8 mA
Factory setting: 22.8 mA, or as speci󹪝ed in order
3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
See also
Setting the fault current of the internal transmitter with switch to ≥ 21 mA (Page 175)
9.4.9.2 Lower saturation limit parameter
Sets the lower threshold for the lower saturation limit.
Parameter assignment
9.4 Assigning parameters using remote operation
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
168 Operating Instructions, 05/2020, A5E41864807-AB