Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Basic communication settings 30.08.2007
6 Basic communication settings
6.1 RM… controllers
6.1.1 Decentral bus power
The type of bus power supply is set on the "Basic settings" operating page, on the
"Decentral bus power supply" line.
Main menu > Commissioning > Communication > Basic settings
Decentral bus power supply, RM… controllers
Default. On
Settings Off / On
In small networks the KNX bus can be operated with the default value "Dec bus
power supp: On". Refer to section 2.2 for information about the bus power supply.
6.1.2 Clock time operation
"Clock time operation" refers to the transmission of the date and time. For the
RM… controllers, this is set on the "Clock time op:" line of the "Basic settings"
operating page.
Main menu > Commissioning > Communication > Basic settings
Clock time mode, RM… controllers
Default. Master
Settings Autonom. / Slave / Master.
Note
Clock time operation:
Master (time master)
Clock time operation:
Slave (time slave)
Clock time operation:
Autonomous
Basic settings
Device address: 10
Dec bus power supp: On
Clock time op: Master
Rem set clock save: Yes
Basic settings
Device address: 10
Dec bus power supp: On
Clock time op: Master
Rem set clock save: Yes
Basic settings
Device address: 10
Dec bus power supp: On
Clock time op: Slave
Rem set clock save: Yes
Basic settings
Device address: 10
Dec bus power supp: On
Clock time op: Autonom
Rem set clock save: Yes