14
TUTORBIT
COSMOGAS
ATTENTION!!! If the DHW mode is “Thermostat”, the Anti-
legionella service cannot be completed. The installer must 
take all necessary precautions to prevent the legionella 
bacteria from growing in order to avoid seriously harming 
the health of people or animals
NOTE!  For  correct  operation  of  the  system,  if  the  hot 
water tank is controlled by a thermostat, the DHW setpoint 
(Parameters->DHW->DHW setpoint)  must  always  be 
higher than the thermostat setpoint.
ATTENTION!!! The parallelism of the tank lling with the 
heating is only guaranteed with mixed heating circuits.
- Unit of measure
Select °C to display the units of measure according to the 
international system. Select °F to display the units of measure 
according to the imperial system.
- Number of Zones
Select the number of heating zones you want to control.
- Anti-legionella 
Select “Yes” if you want to enable the anti-legionella service 
or select “No”.
ATTENTION!!!  Disable  the Anti-legionella  service  can 
seriously harm the health of people or animals.
- Shue pump type
This parameter controls a possible shue pump installed on 
the domestic hot water tank. It can be used for the “Tank load” 
function when there are several hot water tanks connected in 
series, or it can be used for the mix “Anti-legionella” function 
when the hot water tank is also lled by a solar panel.
ATTENTION!!!  With  a  solar  zone,  it  is  very  important 
to  have  an  anti-legionella  shue  pump  that  works.  If 
this pump is missing, the installer must use alternative 
solutions to run the Anti-legionella. Not doing so, could 
seriously harm the health of people or animals.
- Solar
Select “Yes” if you want to ll the domestic hot water tank also 
using a solar panel, or select “No”
- Solar Antistagn.
Select “Yes” if you want to enable the Anti-stagnation function, 
or select “No”
The anti-stagnation system tries to prevent the solar panel 
from boiling, especially in the summer.
NOTE!  Disable  the  Solar Anti-Stagnation  system  can 
cause malfunctions in the lling system of the hot water 
tank using the solar panel.
- Solar Antif.
Select “Yes” if you want to enable the solar antifreeze function, 
or select “No” if you want to disable it.
ATTENTION!!!  Disable  the  solar  antifreeze  system  can 
seriously damage the solar panels.
- Modbus enable
Modbus enable or not if you want to read the Modbus 
parameters of the heat modules.
4 - INSTALLATION
“Distributed power” conguration
Figure 4-10 shows the application diagram of a system where 
all the heat modules are controlled in parallel to produce 
heating, whereas a single module is intended to produce 
domestic hot water. This system, where the power can be 
distributed in a varied way to the DHW or to the heating, is 
subsequently called “Distributed power”.
Figure 4-31 shows the application diagram of a system where 
all the heat modules are controlled in parallel to produce 
domestic hot water. In this case, the modules must be 
“AGUADENS T” water heaters models.
4.7 - Installation
Install the TutorBit in the room where the heat modules are 
installed or nearby, and follow all the electrical connections 
shown in diagrams of Section 4.21.
4.8 - Choosing and setting 
up the system
Some diagrams of the most common systems, with their own 
electrical system and controller setting, are shown in Section 
4.21.
To browse through the menus and edit a parameter, see 
Section 6.4.
Using the Conguration->System  menu, you can access 
the following parameters to set up your system:
- Modules Qty:
number of heat module you want to install in cascade (from 
1 to 4);
- Module 1
Indicates if heat module 1 is used to produce heating and 
DHW in “All power” or “Distributed power” (Section 4.6).
- Module 2
Same function as Module 1, but refers to Module 2.
- Module 3
Same function as Module 1, but refers to Module 3.
- Module 4
Same function as Module 1, but refers to Module 4.
- Outdoor Sensor
Select “Yes” if you want to enable the outdoor sensor and all 
its functions: antifreeze protection and climatic adjustment.
- DHW
Select “Yes” if you want to produce DHW with a storage tank.
- DHW return sensor
The DHW return zone can be controlled with the time 
programme in the menu Parameters->DHW->DHW return 
timer prog. However, if you want to control the return zone 
also based on your temperature, select “Yes” in the “DHW 
return sensor” parameter.
- DHW mode
Select “Sensor” if the hot water tank is controlled by a 
temperature sensor. Select “Thermostat” if the hot water tank 
is controlled by an On-O thermostat.