EasyManua.ls Logo

Siemens TUTORbit POL895 - Heating Zones, DHW, DHW Return, Solar, 2 Tanks (1 for Solar and 1 for Boiler) and Solar Transfer Fun- Ction

Siemens TUTORbit POL895
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50
TUTORBIT
COSMOGAS
4 - INSTALLATION
4.21.11 - 1 heating zones, DHW, DHW return, solar, 2 tanks (1 for solar and 1 for boiler) and solar transfer function
Figure 4-33 - Hydraulic connection
Settings:
Conguration > System >
Number of Modules 1
Module 1 Heating
Outdoor sensor No
DHW Yes
DHW return sensor Yes
DHW Mode Sensor
Unit of measure °C
Number of Zones 1
Antilegionella Yes
Shu󰀪e type pump Antilegionella
Solar Yes
Solar Atistagnation Yes
Solar Antifrost Yes
Modbus enable No
Heat pump No
Conguration > Zones > 3 way valve > 3 way valve 1> Zone type Mix
NOTE: The mixing pump (53) must be set as “Anti-legionella”.
NOTE: The mixing pump (53) also acts as a transfer by means of relay R1.

Table of Contents