5.1.3 C3 Pause time (0.00)
C3 = 0.00 No pause time input possible.
C3 = 0.10 Pause time input possible.
5.1.4 C4 Minimum flap opening time (0.20)
C4 = X.XX
X.XX sec. minimum flap opening time for the flap.
Works setting: 0.20 sec.
5.1.5 C5 Flushing delay (10.0)
C5 = X.XX
X.XX sek. back wash delay time when flap does not operate
correcty
Works setting: 10,0 sec.
5.1.6 C6 Flushing time (1.00)
C6 = X.XX
X.XX sec. flushing time
Works setting: 1,00 sec.
5.1.7 C7 Switch-on delay (0.50)
C7 = X.XX
X.XX sec. switch-on delay after closing the flap.
Works setting: 0.50 sec.
5.1.8 C8 Fault behavior (300)
C8 = X.XX
X.XX sec. Switches off in the event of a fault
Works setting: 0.50 sec.
C8 = 0.00 The control unit does not switch off in the event of a fault.
C8 = 300
The conveying process is switched off after 300 sec. in
the event of a fault
5.1.9 C9 Programming parameters (22.0)
C9 = 22.0
It is possible to select a function (C-function)
It is not possible to change the parameters (P- function)
C9 <> 22.0
It is not possible to select a function (C-function) .
It is possible to change the parameters (P-function) .
C9 = 0.1 The works settings are loaded.
C-parameters are entered between 0.0 and 600.