EasyManua.ls Logo

Sime Format 80 C - 7 Wiring & Functional Diagram; Illustrated Flow Wiring Diagram

Sime Format 80 C
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Supplied By www.heating spares.co Tel. 0161 620 6677
22
7 WIRING & FUNCTIONAL DIAGRAMS
7.1 ILLUSTRATED FLOW WIRING DIAGRAM
5VDC
5VDC
24VRAC
24VAC
24VRAC
240VAC
240VAC
240VAC
240VAC
240VAC
240VAC
24VDC
240VAC
NOTE:
The room thermostat must be connected to the terminals 10-11 of the “TA” connector after
having removed the link.
To remote control the boiler connect an external clock to the terminals 10-11 (24 V) of the
“TAconnector and set the built-in clock to “constant” mode (see user instructions for details).
Fig. 27
JUMPERS POSITION AND FEATURES
JUMPER POSITION AND FEATURE SUPPLY POSITION
CLOSED OPEN
J7 - METANO/GPL Ready to function with LPG Ready to function with natural gas Open
J8 - ANN. RIT.* Ignition delay cancelled Ignition delay operating Open
* In the heating phase, the electronic board is programmed to include a burner technical delay interval of approx. 3 minutes, which occurs both
at system cold starting and at subsequent re-ignitions. The aim is to overcome the problem of repeated ignitions and turning off with very short
time intervals between. This could occur in particular in systems presenting high head losses. At each restart after the period of slow ignition,
the boiler will set itself for about 1 minute at the minimum modulation pressure, and will then move to the heating pressure value set.
JUMPERS

Table of Contents

Related product manuals