6.1.1.2 Four wire base wiring
For four-wire wiring application, use 4098-9682 four-wire base with the following detectors:
4098-9601
4098-9602
4098-9605
4098-9612
4098-9613
4098-9614
4098-9615
When you use the 4098-9682 base, you need to route the auxiliary 24 V power through the 2098-9735 end-of-relay, as shown in Figure 13.
Figure 13: Four wire base wiring
Note:
Only use the Aux-2 resettable Aux power circuit.
Only use four-wire base wiring in Class B wiring style.
6.1.2 IDC wiring specifications
The maximum wiring resistance for each circuit is 50 ohm.
Suggested wire is 18 AWG, allow up to 3500 ft. distance from the control unit to the EOLR Class B.
The maximum detector standby current for each IDC is 3 mA.
The maximum detector alarm current for each IDC is 75 mA.
The maximum ripple for each IDC is 2V peak to peak for a voltage range of 15VDC to 30VDC.
The maximum circuit capacitance for each IDC is 100 μF.
page 21 579-1402 Rev B
2004 Foundation Series Fire Alarm Control Unit Installation Guide