6.7.2 Connecting the DACT using Ethernet lines and the DSC TL300
To connect the DACT using Ethernet lines and the DSC TL300, ensure you adhere to the following guidelines:
1. Mount the control unit containing the TL300 less than 20 ft (6.1 m) from the FACU.
2. The wiring to FACU must be in 20 ft (6.1 m) conduit.
3. Connect the TL300 to the FACU's IDC to monitor LAN connection failure.
4. Only use terminals T2 and R2 of TB2. Do not use auxiliary equipment.
5. For programming and installation, refer to the TL300 Installation Manual.
6. Use the PC tool version 01.00 or later. Select the IP communicator mode from the DACT setting tab.
7. The power supply must be listed for fire applications and the wiring must be in 20 ft (6.1 m) conduit.
8. Use a ferrule connector or a lever nut connector or other suitable multiple wiring connector for the two wires that are shown to
be connected to the one terminal to make sure that only one wire goes to the terminal PGM1 of TL300.
Figure 23: DACT wiring using TL300
page 30 579-1402 Rev B
2004 Foundation Series Fire Alarm Control Unit Installation Guide