6.7.3 Connecting the DACT using Ethernet lines and the Bosch C900V2
To connect the DACT using Ethernet lines and the Bosch C900V2, ensure you adhere to the following guidelines:
1. Mount the AE2 enclosure containing the Bosch C900V2, less than 20 ft (6.1 m) from the FACU.
2. The wiring to FACU must be in 20 ft (6.1 m)conduit.
3. Ground the cabinet.
4. Wire the C900V2 to the FACU's IDC to monitor LAN and board failure.
5. Only use terminals T2 and R2 of TB2. Do not use auxiliary equipment.
6. Refer to the Bosch C900V2 Installation Manual for programming and installation.
7. Use the PC tool version 01.00 or later. Select the IP communicator mode from the DACT setting tab.
8. The power supply must be listed for fire applications and the wiring must be in 20 ft (6.1 m) conduit.
9. Use a ferrule connector or a lever nut connector or other suitable multiple wiring connector for the three wires that are shown to
be connected to the same terminal to make sure that only one wire goes to the terminal of CV900V2.
Figure 24: DACT wiring using C900V2
page 31 579-1402 Rev B
2004 Foundation Series Fire Alarm Control Unit Installation Guide