EasyManua.ls Logo

Simplex 2004 Series - DIP switch SW4

Simplex 2004 Series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.3 Auxiliary relays
There are three on-board relays on the FACU, see Figure 17. The contact rating is 30 VDC at 2 A, 0.35 power factor. Each relay is selected
for normally closed or normally open operation. For information about relay settings see Table 7.
All three relays are non-programmable:
Relay 1 is the default for the common trouble relay and is normally energized. When the control unit is completely powered off, the
default setting of the trouble relay is Off Normal.
Relay 2 is the common alarm and the default setting for Relay 2 is On Until Reset.
Relay 3 is the common supervisory.
Figure 17: Auxiliary relay connections
Table 7: Relay settings
Ref designator Functions Settings Jumper position
Normally closed (default)
1-2 (Left)
P7 Relay 1 contact setting
Normally open
2-3 (Right)
Normally open (default)
1-2 (Left)
P6, P5 Relays 2 and 3 contact setting
Normally closed
2-3 (Right)
6.3.1 Wiring an auxiliary relay
To wire an auxiliary relay, ensure you adhere to the following guidelines:
All wiring is between 18 AWG minimum and 12 AWG maximum.
Conductors test free of all grounds and stray voltages before you connect the auxiliary relay to the control unit and other appliances.
All wiring is unsupervised.
Power all Aux. relay loads from the Aux. power circuit or from a regulated, 24 VDC, power limited power supply that is UL-listed for fire
protective signaling service.
6.4 RS485 Interface
This section describes the RS485 interface. Use the RS485 interface to connect annunciators.
You can connect a maximum two numbers of 2606-9111 annunciators to the 2004-9101 control unit.
6.4.1 Wiring an Annunciator
To wire an annunciator, adhere to the following guidelines:
All wiring is between 18 AWG minimum and 12 AWG maximum.
All wiring is supervised and power limited.
Conductors must test free of all grounds and stray voltages before you connect the annunciator to the unit and other appliances.
For bus style wiring, the maximum wiring limit is 4,000 ft. (1219 m) For bus style wiring, see Figure 19.
Note: Figure 19 shows communication wiring only.
For T-Tap style wiring, the maximum distance to the furthest device is 2,500 ft. (762m). For T-Tap style wiring, see Figure 20. Figure 20
shows communication wiring only.
The maximum wiring capacitance is 0.58 μF.
page 25 579-1402 Rev B
2004 Foundation Series Fire Alarm Control Unit Installation Guide

Table of Contents

Other manuals for Simplex 2004 Series

Related product manuals