VOLTAGE MONITOR BOARD, 562-348
1lU
9*E-t9S ON Q9 IINOW 3E)VllOA
1
I
\
JUMPER 1
JUMPER 2
JUMPER 3
The voltage monitor board is used with the BT controller board. It monitors for the presence or absence of voltage
on four monitor zones (EITHER 1 through 4 OR 5 through 6). Jumpers are used to select whether a zone will be
monitored for the presence or absence of voltage. If the associated zone’s jumper is IN, the zone will be monitored
for the presence of voltage. If its jumper is OUT, the zone will be monitored for the absence of voltage. The
jumpers are identified as follows:
Jumper wire JW-1 is for Zones 1 or 5
Jumper wire JW-2 is for Zones 2 or 6
Jumper wire JW-3 is for Zones 3 or 7
Jumper wire JW-4 is for Zones 4 or 6