12OWOLT RELAY BOARD, 562-322
This relay board contains four relays each with dual
form “C” contacts rated for 2 amps.
There are no supervisory jumper wires associated
with Relay Kl. Kl is used for resetting 4-wire smoke
detectors on fire alarm basic transponders (FABT), or
for a control circuit which does not require supervision
on basic transponders (BT).
Relays K2, K3, and K4 may have their circuits
supervised; however, only 28-volt circuits can be
supervised. If you wish to supervise relays K2, K3, or
K4 you must forfeit monitor points 6, 7, and 8
respectively. To supervise the wiring from a relay to
the device, three wires must be added (see Table 0).
TABLE 0
TO SUPERVISE
K2
ADD
Jumper Wires from P5-6 to P5-5
P6-7 to P6-8
P6-9 to P6-10
K3
Jumper Wires from P5-4 to P5-3
P6-11 to P6-12
P5-7 to P5-8
K4
Jumper Wires from P5-1 to P5-2
P5-9 to P5-10
P5-11 to P5-12