SCC CONTROLLER BOARD, 562-184, REV. L OR HIGHER
Sl
RESET
BAUD RATE SELECTOR
I
-305 ?-
WRITE
JUMPER
(MUST BE REMOVED)
A0
Al
A2
A3
A4
A5
TO
ENABLE-
DISPLAY
CIRCUIT
- 5VDC
ADDRESSSELECTOR
The Status Command Center (SCC) is used to annunciate and/or control monitor and control points. Its controller
board has a switch package (S2) which is used to address the controller and determine if LEDs are to illuminate
during power failure. There is also a switch package (J6), which is used to select the baud rate; a WRITE jumper,
used for programming; and a reset switch (Sl).
The first 6 switches of switch package S2 are used to address the SCC as follows:
SWITCH
BINARY WEIGHT
1
1
2
2
3
4
4 8
5
16
6
32
To obtain the SCC address (one less than the associated transponder number), add the binary weight of the open
switches.