Switch 7 on switch package S2 should ALWAYS be CLOSED. If switch 8, is OPEN, no LEDs will light during a
power loss (unless this switch is overridden by the manual switch on the control panel marked ENABLE
DISPLAY). If switch 8 is CLOSED, LEDs on the SCC will continue to be illuminated during a power failure
regardless of the manual switch position on the control panel.
Switch package J6 is used to select the proper baud rate for the SCC. This must match the baud rate selected
for the communications channel (see Figure 1). This baud rate is USUALLY 4800 baud. Set the switches on J6
as follows:
BAUD RATE
4800
J6-3
2400
J6-5
1200 J6-4
CLOSE
SWITCH