2-2
The following tools and equipment are required for 4005 installation:
1/4-inch flat-tip Screwdriver
Volt-Ohmmeter
Diagonal Cutting Pliers
Wire Strippers
841-990 Field Wiring Diagram
The installer is responsible for safeguarding all 4005 material shipped to the job
site. During system installation, store all 4005 items (including all
documentation) in a clean, dry, and safe place until needed.
1. Remove the back box from the shipping container and lay the back box on a
flat surface.
2. Using the information in Figure 2-1 (below) for reference, install the back
box.
For specific internal wiring directions, refer to Figure 2-1, the back box
installation label inside the back box, and to Field Wiring
Diagram #841-990.
Measurement Box Door
Weight (SEE NOTE 6) 11.5 lb [ 25.3 kg] 7.5 lb [ 16.5 kg]
Height 23-
1
/8 in [58.7 cm] 24 in [61.0 cm]
Width 22-
1
/2 in [57.2 cm] 23-
1
/2 in [59.7 cm]
Rough Opening
(SEE NOTE 2)
23-
1
/8 in [58.7 cm]
22-
1
/2 in [57.2 cm]
SEE
NOTE 1
USE 4 HOLES TO
SECURE BACK BOX
TO THE WALL
TOP
SEE
NOTES
SEE NOTES
SEE NOTES
B
B
B
AA
A
2 & 3
SEE
NOTE 7
4 & 5
4 & 5
CAUTION
:
ENCLOSURE
MUST
BE
LEVEL
AND
PLUMB
WHEN
INSTALLED.
DOOR
1/2-INCH
WALL BOARD
2X4 WALL
STUD
NAIL
KNOCKOUT
Figure 2-1. Back Box Installation
Installation
Tools and Equipment
Back Box Installation
NOTES:
1. BOX CAN BE MOUNTED SEMI-FLUSH WITH THE SURFACE OF THE WALL.
2. DIMENSIONS SHOWN ARE TYPICAL FOR ALL SURFACE AND SEMI-FLUSH
INSTALLATIONS.
3. USE ROUGH OPENING DIMENSIONS WHEN PREPARING SEMI-FLUSH
INSTALLATIONS.
4. "A" CONDUIT DENOTES ONLY NON-POWER LIMITED WIRING.
"B" CONDUIT DENOTES ONLY POWER-LIMITED WIRING.
3/4-INCH KNOCKOUTS ARE PROVIDED.
5. WHEN PROVIDING ADDITIONAL CONDUIT ENTRANCES TO THE BOX, USE A
SUITABLE PUNCH TO PROVIDE SEPARATE CONDUIT ENTRANCES FOR POWER-
LIMTED AND NON-POWER LIMITED WIRING (AC POWER, BATTERY, CITY
CONNECT) AT OPPOSITE ENDS OF BOX, CHECK SYSTEM LABEL ON DOOR FOR
POWER-LIMITED INFORMATION.
6. WEIGHT IS IN POUNDS, AND DOES NOT INCLUDE THE BATTERIES.
7. THIS SPACE MUST BE KEPT FREE OF WIRING FOR BATTERY INSTALLATION.