EasyManua.ls Logo

Simplex 4005 - Warm Start Procedure

Simplex 4005
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-10
The CPU Warm Start button (SW1) located beneath the main display is used to
return the system to its normal state while preserving historical logs,
enable/disable states of points, and the time. When warm starting the 4005, a
Warm Start / Check Time and Date trouble occurs that clears upon
acknowledgment. A warm start is the primary operation used to clear the
Simplex Service Mode trouble.
Handling Abnormal Conditions, Continued
How to Warm Start the
System