3-11
Various Functions may be passcode protected to prevent access by unauthorized
personnel. Passcodes are provided to the user during system installation. To
change or receive additional information concerning your passcodes, contact
your local Simplex Branch Office.
The Menu and its sub-menus (for Access Level 1) are shown in Figure 3-4 below.
MONITO
RELAY
SIGNAL
DIGITAL
ANALOG
HISTORY LOG ALARMS
TROUBLES
COMBINED
SOFTWARE REVISION
PASSCODE LOGIN
LOGOUT
GENERIC OUTPUT
GENERIC INPUT
SYSTEM POINTS
LIST
Figure 3-4. Menu Structure (Access Level 1)
The 4005 has three passcode-protected login levels (Level 1 Operations do not
require a Passcode). Logging in at Level 4 causes a Service Trouble that cannot
be cleared without a warm or cold start of the 4005. The default operations and
their passcodes are shown in Table 3-2 below.
Table 3-2. Login Levels (Access Levels)
LEVEL OPERATIONS LEVEL OPERATIONS
1
Alarm Acknowledge
Trouble Acknowledge
Supervisory Acknowledge
Alarm Silence
System Reset
View Points and Logs
Passcode (Log In / Log Out)
Software Revision
3
All Level 1 & 2 Operations
Clear Logs
Clear Verification Tallies
Walk Test
Programming:
Edit/Clear Point Label
Restore/Save CFIG
2
All Level 1 Operations
Set Time/Date
Enable/Disable Points
4
All Level 1,2, & 3 Operations
Cold Start
Programming:
Edit Cards
Edit SMPL Program
System Options
Edit Access Level
Continued on next page
Passcodes and Access Levels
Overview
Menu Structure
Login\Logout (Passcodes and
Access Levels)