4-3
Chapter 4 IDNAC Power Supply
IDNAC Section
IDNAC Section
Overview
The IDNAC power supply has a single SLC
for connecting addressable IDNAC devices.
The power supply is compatible with
TrueAlertES and TrueAlert Addressable
product lines (both multi and fixed candela).
The IDNAC output is Class B only. Class A
operation requires use of optional module
4007-9804, IDNAC dual Class A isolator.
The output is duplicated on the terminal block
to facilitate “T” tapping on the circuit at the
panel. EOL resistors are not required.
All wiring is supervised and power-limited.
Figure 4-2. IDNAC Terminal
Wiring Wiring Parameters
Table 4-4 identifies the IDNAC wiring parameters that must be considered.
Note: If a shielded wire is used, cut it and tape it.
IDNAC
+ - + -
Specifications
Table 4-3. IDNAC Specifications
Supports
- Up to 12 4905-9929 remote TrueAlert Addressable Isolators per
IDNAC Circuit.
- Up to 30 devices connected directly to any isolator terminal pair*.
- Up to six isolators between any appliance and the IDNAC SLC
terminals. All wiring is 20 AWG to 12 AWG.
*For more information on the isolator, refer to the 4905 Isolator+
Installation Instructions, 574-769.
Electrical Specifications:
Channel Voltage 29.5 VDC nominal.
Circuit Requirements The maximum alarm current is 3 A per circuits.
Isolator
Isolator (DCAI)
To wire an IDNAC as a Class A circuit, the DCAI modules (4007-9804)
is required (2 Class A circuits with fault isolation). For more information
on Dual Class A isolator and on how to calculate Class B wiring with
isolation, refer to the
DCAI Installation Instructions 579-1029
.
Table 4-4. IDNAC Wiring Parameters
IDNAC Wiring Limits
Channel Loading
127 devices (IDNAC devices or other compatible devices). Refer
to the Compatible Devices and Appliances section for more
details.
Max. wiring distance
Max. cable load 10,000 ft (3,048m) per channel.
Max. wire length from
panel to any device
4,000ft (762m).