Chapter 5 4007ES Power Supplies
IDNet Section, Continued
Device
Addressing
(Class A and
Class B)
If no remote isolators or isolator bases are on the loops, device addressing can be assigned
without concern for sequence.
If remote isolators or isolator bases are on the loops, the required addressing approach
is to start from the “B” side and assign each successive isolator a higher address than the
isolator it precedes.
For Class B wiring only, the “A” output and “B” output per loop are connected together
in parallel via a jumper.
Wiring Wiring Parameters
Table 5-2 identifies the IDNet wiring parameters that must be considered when installing this
card. For additional wiring information, refer to document 900-408, Simplex Addressable Fire
Alarm Panels Field Wiring Specifications.
Table 5-2. IDNet Wiring Parameters
IDNet Wiring Capacitance Parameters
Parameter Value
Maximum Supported Channel Capacitance The sum of line-to-line capacitance, plus the capacitance of
either line-to-shield (if shield is present) = 0.6 µF
IDNet Wiring Class A and Class B Limits
Channel Loading Up to 125 devices 126 to 250 devices
Max. resistance to compatible devices.
(Include the 2081-9044 Overvoltage
Protector resistance when applicable)
50 ohms maximum 35 ohms maximum
Maximum wiring distance*:
(18 AWG, 16 AWG, 14 AWG, 12 AWG)
4000 ft (1219 m) 2500 ft (762 m)
*Notes:
The "maximum wiring distance" is the maximum
distance from both the IDNet control terminals (primary
and return) to the farthest device on the circuit. See
Figure 5-2.
Maximum wiring distance is determined by either
reaching the maximum resistance, the maximum
capacitance, or the stated maximum distance,
whichever occurs first.
The total circuit cable load (amount of cable used) must
not exceed 12,500ft (3,8km).
Figure 5-2. Maximum Wiring Distance
IDNet Wiring Considerations
using 2081-9044 Overvoltage
Protectors
(2081-9044 is UL listed to
Standard 1459, Standard for
Telephone Equipment)
External wiring must be shielded (for lightning suppression) and 2081-9044
Overvoltage Protectors must be installed at building exit and entrance locations.
For more information, refer to the Model 2081-9044 Overvoltage Protector Installation
Instructions, 579-832.
Capacitance; each protector adds 0.006 µF across the connected line.
Resistance; each protector adds 3 ohms per line of series resistance; both IDNet wires
are protected; 6 ohms per protector will be added to total loop resistance.
Maximum distance of a single protected wiring run is 3270 ft (1 km).
Refer to document number 574-832, 2081-9044 Overvoltage Protector Installation
Instructions, for additional information.
XXXX ft maximum to
farthest device from
either end of loop
Device
Device
Device
Control Terminals
(Class A wiring example)
Device
Control Terminals
(Class B wiring example)
Device
Device
Total cable load
must not exceed
12,500ft (3,8km)
Device