EasyManua.ls Logo

Simplex 4007ES Hybrid - Chapter 6 Optional Modules and Cards

Simplex 4007ES Hybrid
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-1
Chapter 6
Optional Modules and Cards
Introduction The 4007ES can be ordered with a variety of optional cards and modules, depending on the
needs.
8-point Zone/
Relay Card
The 8-point zone/relay card (4007-9801) mounts in the 4007ES panel. Up to four cards can be
added. Each card allows the monitoring of up to eight Class B or four Class A zones, or eight
relay contacts.
For more information on the 8-point zone/relay card, refer to manual 579-1103.
25V Regulator
Module
The 25V regulator module (4007-9802) regulates the panel power supply output received
from the NAC power supply (4007ES) or the IDNAC power supply (4007ES hybrid) to a
25VDC level. The 25VDC regulated output is isolated from the panel and complies with
power-limited requirements.
For more information on the 25V regulator module, refer to manual 579-812.
IDNet+ Loop
Expansion Card
The IDNet+ loop expansion card (4007-9803) mounts directly on the IDNAC/NAC power
supply.Up to two cards can be added. Each card adds a single Class A/Class B IDNet+ loop
and increases the device capacity by 75 points.
For more information on the IDNet+ loop expansion card, refer to manual 579-1106.
LED Module The LED module (4007-9805) allows the operator to view the simultaneous signaling of an
alarm and trouble conditions on up to 24 zones. All the LEDs have configurable colors, red or
yellow, except the LEDs in the last column, which are configurable as red or green.
For more information on the LED module, refer to manual 579-1105.
SDACT Card The SDACT card (4007-9806) can be mounted in the 4007ES panel. It is used to notify a
central station when an event occurs, to report changes to a specific point, to be connected to a
transmitter for connection to a central station.
For more information, refer to manual 579-954.
City Circuit The city circuit card with disconnect switches (4007-8907) and without disconnect switches
(4007-9808) are used to annunciate alarms and other urgent indications to remote facilities.
Each city circuit module has two configurable circuits (alarm, trouble, or supervisory
reporting) and supports Reverse Polarity and Local Energy Master Box Applications. Only
one city card can be installed per system. It is not available when an alarm relay is used.
For more information on city circuits cards, refer to manual 579-955.
In this chapter
8-point Zone/Relay Card ...................... 6-1 25V Regulator Module.......................... 6-1
IDNet+ Loop Expansion Card .............. 6-1 LED Module ......................................... 6-1
SDACT Card......................................... 6-1 City Circuit............................................ 6-1
Alarm Relay Card ................................. 6-2 TrueInsight Service Gateway ................ 6-2
Dual Class A Isolator............................ 6-2 Example of Combinations..................... 6-2