EasyManua.ls Logo

Simplex 4007ES Hybrid - NAC Troubleshooting

Simplex 4007ES Hybrid
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-6
Chapter 3 NAC Power Supply
Troubleshooting
Troubleshooting Table 3-7 gives the LED definition for the NAC power.
Table 3-7. 4007ES Hybrid Indicator LEDs
Figure 3-5. LEDs on the 4007ES Hybrid Power Supply
LED10 AC
Green. Off on AC failure
LED2 RUI Trouble Yellow. On for Class A RUI trouble
LED6 RUI OC Yellow. Indicates a short (overcurrent)
LED3 Comm
Yellow. Indicates that the communication between the NAC power sup-
ply and the CPU is lost
LED 4 Gen Power
Steady On, yellow. Indicates AC power loss, earth fault, overcurrent
and battery trouble
LED5, 7, 8,
and 9
NAC 1, 2, 3,
4
Steady On, yellow. Used to signal overcurrent, short, and open
circuit.
LED1 Aux/SNAC
Steady On, yellow. Use to signal overcurrent, short, and open
circuit.
LEDs
Aux/SNAC
Comm
Gen Power
NAC1
NAC2
NAC3
NAC4
LEDs
RUI TBL
RUI OC

Table of Contents