EasyManua.ls Logo

Simplex 4007ES Hybrid - NAC Class A Wiring; NAC Class B Wiring

Simplex 4007ES Hybrid
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-5
Chapter 3 NAC Power Supply
NAC Section, Continued
Wiring Class A Wiring
Note: The Class A wiring style is set up in the programmer. Refer to the 4007ES Programmer’s manual,
579-1167, for more information.
To connect the power
supply to reverse-polarity,
non-addressable
notification appliances
using Class A wiring:
1. Route wire from the
“B+” and “B-” outputs of
the power supply to the
appropriate inputs on a
peripheral notification
appliance. Use NAC1,
NAC2, NAC3 or NAC4
(2.).
2. Route wire from the first
appliance to the next
one. Repeat for each
appliance.
Figure 3-3. Class A NAC Wiring
3. Route wire from the last appliance to the A+ and A- inputs on the same NAC circuit of the
power supply.
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the 10 KOhms, ½ W, brown/black/orange resistor (378-030) on each unused circuit.
No external end-of-line resistor is needed for circuits in use.
Class B Wiring
Note: The Class B wiring style is set up in the programmer. Refer to the 4007ES Programmers
manual, 579-1167, for more information.
To connect the power
supply to appliances using
Class B wiring:
1. Route wire from the B+,
B- outputs on TB2 and
TB3 of the power sup-
ply to the appropriate
inputs on a peripheral
notification appliance.
Use NAC1, NAC2,
NAC3, or NAC4.
2. Route wire from the first
appliance to the next
one. “T” tapping is not
allowed. Repeat for
each appliance.
Figure 3-4 Class B NAC Wiring
3. Route wire from the last appliance to the EOLR harness (10KOhms, 1/2 W: P/N 733-894).
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Leave the factory installed EOL Resistor (10 KOhms*, ½ W; brown/black/orange) on each
unused circuit. The circuit must connect “B+” to “B-” terminals.
6. Document EOL value in panel per circuit.
*If using a 4007ES hybrid panel, keep the original value and set the programmer accordingly.
2
TYPICAL
APPLIANCE
RED BLK
TYPICAL
APPLIANCE
10K 1/2W (133-894)
RED RED
RED RED
12 AWG (3.309 mm
2
) to
18 AWG (0.8231 mm
2
)
BLK
BLK
BLK
4081-9008 EOL Harness
Leave the factory installed
EOL Resistor (10 KOhms,
½ W, brown/black/orange)
on unused circuits
NAC1
B+ B- A+ A-
NAC2
B+ B- A+ A-
NAC3 NAC4
B+ B- A+ A- B+ B- A+ A-

Table of Contents

Other manuals for Simplex 4007ES Hybrid

Related product manuals