5 Accessories
This section contains information about relay module accessories.
5.1 2098-9737 Relay Module wiring
The 2098-9737 Relay module is used with the 4098-9791 Sensor Base. Install the relay module using the Figure 14 and Figure 20 as a
reference.
Figure 20: 2098-9737 Relay Module Wiring
Note:
1. 18 VDC to 32 VDC 24 mA typical / 35 mA maximum.
2. Contact A or B: dry, Form C, each rated 3 A at 28 VDC / 115 VAC, resistive.
3. The maximum wire length between the 4098-9791 sensor and the relay module is 100 feet, or 30.48 meters.
5.2 4098-9860 Relay Module wiring
The 4098-9860 Relay Module is used with the 4098-9780 Sensor Base. Install the relay module using Figure 14 and Figure 21 as a
reference.
Figure 21: 4098-9860 Relay Module wiring
Note:
1. Maximum wire length between sensor 4098-9780 and relay module is 100 ft.
2. Contact Dry Form C, rated at 2 A at 30 VDC / 0.5 A at 125 VAC, resistive.