3
 
 
The procedures that follow are used to install the 4098-9755 or 4098-9756 
addressable duct sensors.  See Figure 1 for the location of the duct sensor DIP 
switches.  The instructions provided show how to set the address at each sensor 
and also how to make electrical connections.  Addressable smoke duct sensors are 
connected to a 2120 Multiplex Communicating Device Transponder (CDT), 4010 
Fire Alarm Panel, 4020 Fire Alarm Panel, 4100+ Fire Alarm Panel, or 4120 Fire 
Alarm Panel by a single twisted-shielded wire pair (MAPNET II/IDNet). 
 
Duct sensor addressing is critical since the 2120 Communicating Device 
Transponder (CDT), 4010, 4020, 4100+, and 4120 Systems report alarms and 
troubles per duct sensor rather than per zone.  Each duct sensor has a unique 
address.  This address is associated with a custom label which identifies its 
physical location within a building.  The duct sensor’s address and location must 
match up with the address listed in the specification sheets of the 2120 Job 
Configuration Report or Programmer’s Report for the 4010, 4020, 4100+, or 
4120 System.  You should have the appropriate specification sheets with you 
during this part of the installation. 
 
1.  Using the 2120 Job Configuration Report, find the entry for the duct sensor 
you are about to install.  The CUSTOM LABEL column provides the 
location while the DEVICE ADDRESS column provides the switch setting 
data. 
 
2.  Using the switch setting data for the duct sensor you are installing set the 
duct sensor’s address using Figure 3.  Loosen the four screws securing the 
clear plastic cover to the housing base.  Locate the DIP switch on the duct 
sensor’s PCB assembly in the wiring compartment (see Figure 1).  Use a 
small screwdriver or pen to set the switches. 
 
For the switch setting data in the DEVICE ADDRESS column, “1” is switch 
ON while “0” is switch OFF. 
 
3.  Recheck the location of the sensor and its address before electrical 
installation.  Mark an address label with the appropriate address for your 
duct sensor by shading a label box for each sensor DIP switch in the ON 
position.  Then apply the label to the sensor near the sensor’s DIP switches. 
 
4.  Secure the duct sensor’s clear plastic cover to the housing using the four 
screws  (Torque screw to 8-10 inch-pounds). 
 
1.  Using the System Point Summary for the 4010, 4020, 4100+, or 4120, find 
the entry for the duct sensor you are about to install.  The ZONE NAME 
(with a “M” prefix) and CUSTOM LABEL are located in the SYSTEM 
POINT SUMMARY. 
 
For example, Address M1-7 (for the 4010, 4100+, or 4120 System) is 
shaded in Figure 2.  M1 is the addressable channel while -7 is the device 
address on the channel.  For a duct sensor with Address M1-7, address 7 
must be set on the duct sensor’s DIP switches.  Address 7 is illustrated in 
Figure 3. 
 
Continued on next page 
Setting the Duct Sensor’s Address 
Addressable Duct Sensors 
4098-9755 or 4098-9756 
(MAPNET II/IDNet) 
General 
Address Setting for the 2120 
CDT System (use with  
4098-9755 only) 
Address Setting for the 4010, 
4020, 4100+, or 4120 
Technical Manuals Online! - http://www.tech-man.com