6 S4100-0034-12 3/2012
Amplifier and Related Audio Options (Continued)
Model Description Details and Mounting Reference
4100-5116
Expansion Signal Module; three, 1.5 A Class B
NACs; up to five maximum per amplifier; NAC
rating = 1.5 A, 50 W, or 100 speakers maximum
Converts one NAC input to three NAC outputs; selects between two inputs;
for Flex-35/50 amplifiers only, two input NACs are required; Single Block
module mounts in expansion bay; Supv. = 20 mA; Alarm = 80 mA
4100-1266
Expansion Signal Module NAC Expander; NAC
rating = 1.5 A, 50 W, or 100 speakers maximum
Expands module capacity to six, Class B NACs;
Supv. = 0.84 mA; Alarm = 60 mA
These modules
mount on the
4100-5116;
select one max.
per 4100-5116
as required
4100-1267
Expansion Signal Module Class A Adapter; NAC
rating = 1.5 A, 50 W, or 100 speakers maximum
Converts 3 Class B, NACs to Class A; Supv. = 1 mA;
Alarm = 30 mA
4100-1268
Expansion Signal Module Constant Supervision
Adapter for 25 VRMS or 70.7 VRMS; NAC rating
= 1.4 A, 50 W, or 100 speakers maximum
Converts 3 Class B NACs to Class B or Class A Constant
Supervision NACs; Supv. = 38 mA on batteries (constant
supervision deactivated); Alarm = 70 mA
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 k
, 1 W
4100-2300 Expansion Bay Hardware; order one for each expansion bay
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
Audio Input and Controller Options (see page 2 for custom message ordering)
Model Description Details and Mounting Reference
4100-1240
Auxiliary Audio Input Module; four additional
(unsupervised) inputs per module; 2 maximum
Inputs for 10 VRMS, 25 VRMS, 70.7 VRMS, line level (0.707 VRMS), or
microphone; 1 Block; current = 10 mA
4100-1241 8 Minute Message Expansion Module
Provides 8 minutes at normal resolution or 4 minutes at high
resolution, Supv. = 2 mA; Active = 17 mA
Mounts to
audio
controller
module
4100-1242 32 Minute Message Expansion Module
Provides 32 minutes at normal resolution or 16 minutes at
high resolution; Supv. = 2 mA; Active = 17 mA
Operator Interface and Related Options
Model Description Details and Mounting Reference
4100-1243
Microphone Module (mike); for Fire Alarm
Control Panels
One maximum per audio system; front panel module that
requires 2 Slots (4”), locate on expansion bay only; space
behind for 4100ES flat modules only
Supervisory
current =
2.4 mA
Active
current =
6 mA
4100-1244
Remote Microphone Module; for Remote
Annunciator Panels
Front panel module that requires 2 Slots (4”), locate on
expansion bay only; space behind for 4100ES flat modules
only; distance limited to 4000 ft (1219 m)
4100-1252 1 Channel (audio or mike)
Operator
Interface
LED/Switch
Modules
Single Slot LED/switch modules; connects to a 4100-1288 or 4100-1289
LED/switch controller in the same bay; space behind controller accepts
4100ES flat modules only (see drawings on p. 4); current = 24 mA;
Additional adjacent LED/switch modules, as shown on p. 4, are used as
required for specific speaker circuit selection (refer to data sheet
S4100-0032 for LED/switch module availability)
4100-1253 1.5 Channel (audio + mike)
4100-1254 2 Channel (full audio)
4100-1255
3-8 Channel (8 channel normal
res. messages, 4 channels of high
res. messages)
4100-1288
64 LED/64 Switch Controller
Module with mounting plate
Refer to
data sheet
S4100-0032
for details
Mounts behind the LED/switch modules; has
provisions for one 4100-1289 Controller Module
LED/switch controllers
and their connected
modules must be in
the same bay
4100-1289
64 LED/64 Switch Controller
Module without mounting plate
Mounts on extra space of 4100-1288; controls
additional 64 LEDs and 64 switches
Firefighter Telephone System Products
Model Description Details and Mounting Reference
4100-1270
Master Telephone with Control Module and
three Class B telephone NACs, one maximum
per audio system; for use in Fire Alarm Control
Panels only; includes one 4100-1272 Module
Front panel module; space behind for 4100ES flat modules only; phone
control module included, mounted on bay module mounting plate; for
individual telephone circuit control, use LED/switch modules;
Supv. = 80 mA; in use = 140 mA + remote phones (see table on page 7)
4100-1271 Remote Master Telephone Mounts in Remote Annunciator Panel only (see S4100-0038)
4100-1272
Expansion Telephone Control Module with three
Class B telephone NACs
Expansion module for additional telephone circuits in main control or
transponders; Supv. = 80 mA; in use = 140 mA + remote phones
4100-1273 Telephone NAC Class A Adapter Module Mounts to 4100-1270 or -1272; no additional current required
Network and MINIPLEX Transponder Audio Connection Options
Model Description Details
4100-0623
Network Audio Riser Controller Module for
control of either an analog or digital riser module
Typically for Network nodes without an audio controller, used for NAA
applications; mounts in Block A; current = 35 mA
4100-0621
Dual Channel Analog Audio Riser
Module
Select one,
mounts in
Block B
Accepts two separate audio signals from host; controlled by Transponder
Interface Module; current = 25 mA when active
4100-0622
3-8 Channel Digital Audio Riser
Module; with NAA input
Receives and decodes digital inputs; up to eight audio channels;
current = 70 mA; NAA input for 25, 70.7, or 0.707 VRMS
4100-1341
MCC (Multiple Command Center)
Digital Audio Riser Interface
Selects a single digital audio channel and converts it to an analog line level
for input to an analog 4100ES/ 4100U/4100 Legacy voice panel; current =
70 mA
4100-9854 4100/4100+ Legacy bay mounting kit Use to mount 4100-1341 MCC Digital Audio Riser Interface in legacy panel
4100-1258
NPU to 4100ES Audio Interconnect Module;
mounts in 4100ES Audio cabinet
Dual terminal block module with harnesses for connecting to the Audio
Controller and Telephone Control module (requires 1 Block)
Emergency Voice/Alarm Communications Equipment Product Selection (Continued)

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing