5 S4100-0034-12 3/2012
Analog Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible
Model Description Details
4100-9620
Basic Analog Audio Operation with microphone, requires
dedicated expansion bay
Includes: Expansion Bay, 4100-1210 Analog Controller Board,
Microphone Module, and Audio Expansion Bay Kit
4100-1210
Analog Controller Board only; order expansion bay and
audio expansion bay kit separately
Controller board mounts in Blocks A and B
4100-1361 25 VRMS output
Flex-35, 35 W Amplifier, constant
supervision compatible
NAC rating = 1.4 A
35 W, or 100
speakers max.
Includes three on-
board Class B audio
NACs; power is
supplied from an XPS,
RPS, or SPS*
4100-1362 70.07 VRMS output NAC rating = 0.5 A
4100-1312 25 VRMS output
Flex-50, 50 W Amplifier, constant
supervision compatible
NAC rating = 2 A
50 W, or 100
speakers max.
4100-1313 70.7 VRMS output NAC rating = 0.707 A
100 W Analog Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
Power Supply Input/Listing Description Details
25 VRMS 70.7 VRMS
4100-1314 4100-1315 120 VAC, 60 Hz UL
Primary
100 W
Amplifier
Includes six, Class B audio NACs;
NAC rating = 100 speakers maximum;
2 A @ 25 VRMS (50 W);
1.414 A @ 70.7 VRMS (100 W)
ULC
models
have low
battery
dropout
circuit
4100-1316 4100-1317 120 VAC, 60 Hz ULC
4100-1318 4100-1319 220/230/240 VAC, 50/60 Hz UL
4100-1320 4100-1321 120 VAC, 60 Hz UL
Backup
100 W
Amplifier
Uses the six Class B NACs of primary
amplifier
4100-1322 4100-1323 120 VAC, 60 Hz ULC
4100-1324 4100-1325 220/230/240 VAC, 50/60 Hz UL
Digital Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible
Model Description Details
4100-9621
Basic Digital Audio Operation with microphone, requires
dedicated expansion bay
Includes: Expansion Bay, 4100-1311 Digital Controller Board,
Microphone Module, and Audio Expansion Bay Kit
4100-1311
Eight Channel Digital Controller Board only; order
expansion bay and audio expansion bay kit separately
Controller board mounts in Blocks A and B
4100-1363 25 VRMS output
Flex-35, 35 W Amplifier, constant
supervision compatible
NAC rating = 1.4 A
35 W, or 100
speakers max.
Includes three on-
board Class B audio
NACs; power is
supplied from an XPS,
RPS, or SPS*
4100-1364 70.07 VRMS output NAC rating = 0.5 A
4100-1326 25 VRMS output
Flex-50, 50 W Amplifier, constant
supervision compatible
NAC rating = 2 A
50 W, or 100
speakers max.
4100-1327 70.7 VRMS output NAC rating = 0.707 A
100 W Digital Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
Power Supply Input/Listing Description Details
25 VRMS 70.7 VRMS
4100-1328 4100-1329 120 VAC, 60 Hz UL
Primary
100 W
Amplifier
Includes six, Class B audio NACs;
NAC rating = 100 speakers maximum;
2 A @ 25 VRMS (50 W);
1.414 A @ 70.7 VRMS (100 W)
ULC
models
have low
battery
dropout
circuit
4100-1330 4100-1331 120 VAC, 60 Hz ULC
4100-1332 4100-1333 220/230/240 VAC, 50/60 Hz UL
4100-1334 4100-1335 120 VAC, 60 Hz UL
Backup
100 W
Amplifier
Uses the six Class B NACs of primary
amplifier
4100-1336 4100-1337 120 VAC, 60 Hz ULC
4100-1338 4100-1339 220/230/240 VAC, 50/60 Hz UL
Audio Options for use with either Analog or Digital Systems (see page 2 for custom message ordering)
Amplifier and Related Audio Options
Model Description Details and Mounting Reference
4100-1245
Flex-35/50 Expansion NAC Module; adds
three Class B audio NACs
Choose
one per
amplifier
Mounts on Flex-35/50 assembly; NAC ratings = 1.5 A, 35/50 W,
or 100 speakers maximum; Supv. = 8.4 mA, Alarm = 60 mA
4100-1246
Flex-35/50 Class A Adapter Module; converts
three on-board NACS to Class A operation
Mounts on Flex-35/50 assembly; NAC ratings = 2 A, 50 W, or
100 speakers maximum; Supv. = 1 mA, Alarm = 30 mA
4100-1248
100 W Amplifier Expansion NAC Module; NAC
ratings = 1.5 A, 50 W, or 100 speakers max.
Choose
one per
amplifier
Provides six additional Class B audio NACs, mounts on 100 W
amplifier assembly; Supv. = 17 mA, Alarm = 60 mA
4100-1249
100 W Class A Adapter Module; NAC ratings
= 2 A, 50 W, or 100 speakers maximum
Converts six on-board NACs to Class A operation, mounts on
100 W amplifier assembly; Supv. = 1 mA, Alarm = 60 mA
4100-1259
25 VRMS Output; NAC
rating = 2 A, 50 W, or 100
speakers maximum
Constant Supervision
Adapter for three NACs;
select per amplifier output
(not compatible with
amplifier NAC expansion
modules)
Supv. = 10 mA
on batteries;
Alarm = 35 mA
Converts three Class B audio NACS to Class A
or Class B Constant Supervision NACs; mounts
on Flex-35/50 or 100 W amplifier assembly;
use two for the six NACs on 100 W amplifiers;
4100-1260
70.7 VRMS Output; NAC
rating = 0.707 A, 50 W, or
100 speakers maximum
Supv. = 38 mA
Alarm = 70 mA
* Refer to data sheet S4100-0031 for power supply details. (continued on next page)
Emergency Voice/Alarm Communications Equipment Product Selection
NOTE: Select systems as either analog or digital (refer to pg. 7 for mounting reference and pg. 8 for additional specifications)