5 S4100-0034-12 3/2012
Analog Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible
Model Description Details
4100-9620
Basic Analog Audio Operation with microphone, requires
dedicated expansion bay
Includes: Expansion Bay, 4100-1210 Analog Controller Board,
Microphone Module, and Audio Expansion Bay Kit
4100-1210
Analog Controller Board only; order expansion bay and
audio expansion bay kit separately
Controller board mounts in Blocks A and B
4100-1361 25 VRMS output
Flex-35, 35 W Amplifier, constant
supervision compatible
NAC rating = 1.4 A
35 W, or 100
speakers max.
Includes three on-
board Class B audio
NACs; power is
supplied from an XPS,
RPS, or SPS*
4100-1362 70.07 VRMS output NAC rating = 0.5 A
4100-1312 25 VRMS output
Flex-50, 50 W Amplifier, constant
supervision compatible
NAC rating = 2 A
50 W, or 100
speakers max.
4100-1313 70.7 VRMS output NAC rating = 0.707 A
100 W Analog Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
Power Supply Input/Listing Description Details
25 VRMS 70.7 VRMS
4100-1314 4100-1315 120 VAC, 60 Hz UL
Primary
100 W
Amplifier
Includes six, Class B audio NACs;
NAC rating = 100 speakers maximum;
2 A @ 25 VRMS (50 W);
1.414 A @ 70.7 VRMS (100 W)
ULC
models
have low
battery
dropout
circuit
4100-1316 4100-1317 120 VAC, 60 Hz ULC
4100-1318 4100-1319 220/230/240 VAC, 50/60 Hz UL
4100-1320 4100-1321 120 VAC, 60 Hz UL
Backup
100 W
Amplifier
Uses the six Class B NACs of primary
amplifier
4100-1322 4100-1323 120 VAC, 60 Hz ULC
4100-1324 4100-1325 220/230/240 VAC, 50/60 Hz UL
Digital Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible
Model Description Details
4100-9621
Basic Digital Audio Operation with microphone, requires
dedicated expansion bay
Includes: Expansion Bay, 4100-1311 Digital Controller Board,
Microphone Module, and Audio Expansion Bay Kit
4100-1311
Eight Channel Digital Controller Board only; order
expansion bay and audio expansion bay kit separately
Controller board mounts in Blocks A and B
4100-1363 25 VRMS output
Flex-35, 35 W Amplifier, constant
supervision compatible
NAC rating = 1.4 A
35 W, or 100
speakers max.
Includes three on-
board Class B audio
NACs; power is
supplied from an XPS,
RPS, or SPS*
4100-1364 70.07 VRMS output NAC rating = 0.5 A
4100-1326 25 VRMS output
Flex-50, 50 W Amplifier, constant
supervision compatible
NAC rating = 2 A
50 W, or 100
speakers max.
4100-1327 70.7 VRMS output NAC rating = 0.707 A
100 W Digital Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
Power Supply Input/Listing Description Details
25 VRMS 70.7 VRMS
4100-1328 4100-1329 120 VAC, 60 Hz UL
Primary
100 W
Amplifier
Includes six, Class B audio NACs;
NAC rating = 100 speakers maximum;
2 A @ 25 VRMS (50 W);
1.414 A @ 70.7 VRMS (100 W)
ULC
models
have low
battery
dropout
circuit
4100-1330 4100-1331 120 VAC, 60 Hz ULC
4100-1332 4100-1333 220/230/240 VAC, 50/60 Hz UL
4100-1334 4100-1335 120 VAC, 60 Hz UL
Backup
100 W
Amplifier
Uses the six Class B NACs of primary
amplifier
4100-1336 4100-1337 120 VAC, 60 Hz ULC
4100-1338 4100-1339 220/230/240 VAC, 50/60 Hz UL
Audio Options for use with either Analog or Digital Systems (see page 2 for custom message ordering)
Amplifier and Related Audio Options
Model Description Details and Mounting Reference
4100-1245
Flex-35/50 Expansion NAC Module; adds
three Class B audio NACs
Choose
one per
amplifier
Mounts on Flex-35/50 assembly; NAC ratings = 1.5 A, 35/50 W,
or 100 speakers maximum; Supv. = 8.4 mA, Alarm = 60 mA
4100-1246
Flex-35/50 Class A Adapter Module; converts
three on-board NACS to Class A operation
Mounts on Flex-35/50 assembly; NAC ratings = 2 A, 50 W, or
100 speakers maximum; Supv. = 1 mA, Alarm = 30 mA
4100-1248
100 W Amplifier Expansion NAC Module; NAC
ratings = 1.5 A, 50 W, or 100 speakers max.
Choose
one per
amplifier
Provides six additional Class B audio NACs, mounts on 100 W
amplifier assembly; Supv. = 17 mA, Alarm = 60 mA
4100-1249
100 W Class A Adapter Module; NAC ratings
= 2 A, 50 W, or 100 speakers maximum
Converts six on-board NACs to Class A operation, mounts on
100 W amplifier assembly; Supv. = 1 mA, Alarm = 60 mA
4100-1259
25 VRMS Output; NAC
rating = 2 A, 50 W, or 100
speakers maximum
Constant Supervision
Adapter for three NACs;
select per amplifier output
(not compatible with
amplifier NAC expansion
modules)
Supv. = 10 mA
on batteries;
Alarm = 35 mA
Converts three Class B audio NACS to Class A
or Class B Constant Supervision NACs; mounts
on Flex-35/50 or 100 W amplifier assembly;
use two for the six NACs on 100 W amplifiers;
4100-1260
70.7 VRMS Output; NAC
rating = 0.707 A, 50 W, or
100 speakers maximum
Supv. = 38 mA
Alarm = 70 mA
* Refer to data sheet S4100-0031 for power supply details. (continued on next page)
Emergency Voice/Alarm Communications Equipment Product Selection
NOTE: Select systems as either analog or digital (refer to pg. 7 for mounting reference and pg. 8 for additional specifications)

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing